⚡ TT Systems Made Simple: How Fault Protection Really Works
- MTS DNC ENERGY CONSULTANTS LIMITED

- Jan 3
- 2 min read

In TT electrical systems, safety depends on how quickly faults are disconnected. Whether you're an electrician, designer, or homeowner, understanding how RCDs and fault‑loop impedance work is essential for safe installations.
This guide breaks down the key rules from I.S. 10101:2020+A1:2024, including formulas, examples, and the logic behind the Zₛ tables.
🔌 What Is a TT System?
A TT system connects all exposed metal parts (sockets, appliances, enclosures) to an earth electrode. Unlike TN systems, the installation does not rely on the distributor’s earth.
Because the earth path is through soil, fault currents are often much lower, so the system must rely on RCDs or very low Zₛ to disconnect faults safely.
✅ Fault Protection with RCDs
In TT systems, RCDs are the primary method of fault protection. They trip when they detect current leaking to earth.
The safety condition is:

Where:
( RA ) = resistance of the earth electrode + protective conductor
( IΔn} ) = RCD rated residual current
50 V = maximum safe touch voltage
🔍 Example
RCD rating: 30 mA

In practice, TT systems aim for Rₐ ≤ 200 Ω to ensure reliable tripping under all conditions.
🔧 Fault Protection with Overcurrent Devices (MCBs, Fuses)
Overcurrent devices can be used in TT systems — but only if the fault‑loop impedance is permanently low.
The rule is:

Where:
( Zs ) = fault‑loop impedance
( IA ) = current that causes the device to trip within the required time
( U0 ) = nominal voltage to earth (230 V)
🔍 Where Does ( IA ) Come From?
This is the part most people misunderstand.
MCBs do not trip at a single current — they trip within a range:
Type B: 3–5 × In
Type C: 5–10 × In
Type D: 10–20 × In
✔ The standard uses the upper end of the range
This is the key point.
When I.S. 10101 creates the Zₛ tables (41.2 / 41.3), it assumes:
Type B → 5 × In
Type C → 10 × In
Type D → 20 × In
This produces a lower Zₛ, ensuring the device will trip even in the worst‑case scenario.
📉 Example: Type C 20 A MCB
Using the standard’s assumption (10×In):
IA=10xIn=10x20A=200A
Zₛ=230V/200A=1.15Ω
🧠 Final Takeaway
TT systems rely primarily on RCDs for fault protection.
Overcurrent devices can be used only if Zₛ is very low.
The Zₛ tables in I.S. 10101 are calculated using the upper end of the MCB tripping range (5×In, 10×In, 20×In).
This ensures the device will trip even in the worst‑case scenario.
When verifying an installation, you must compare your measured Zₛ to the table value, not your own calculation using the lower multiplier.
This keeps the installation safe, compliant, and predictable under all conditions.